3C10KS-LCD
UNIT PRICE : 63,425,950 VND
(not include VAT)
BATTERY NOT INCLUDED – 3-phase in 1 phase out UPS series with dual conversion technology, advanced processor, ideal for equipment backup… – Convenient and easy installation, operation and maintenance Easy – High performance – LCD display provides all the information related to UPS power and operation – Scalability and multi-layer protection – Remote management solution combined with external devices vi – Used for network equipment, telecommunications, security, defense, industrial equipment, medical, automation, radio and television…
| INSERT SOURCE | |
|---|---|
| Nominal voltage | 380VAC (L-L) / 220VAC (L-N) |
| Voltage threshold | 208VAC ~ 476VAC (120VAC ~ 275VAC: Full load) |
| Phase number | 3 phase (Star form – 4 wires + ground wire) or 1 phase |
| Nominal frequency | 50/60 Hz (40 ~ 70 Hz) |
| Power Factor | ≥ 0.95 (Single phase input) |
| Generator compatible | Yes |
| OUTSOURCE | |
| Capacity | 10 KVA/9 KW |
| Voltage | 220VAC can be set 230/240VAC ± 1% |
| Phase number | 1 phase (2 wires + ground wire) |
| Waveform | True sine wave in all grid states and independent of the remaining capacity of the battery source. |
| Frequency | Sync to input source 50/60Hz ± 4Hz or 50/60Hz ± 0.05Hz (battery mode) |
| Performance | ≥ 93.5% battery (>98% ECO Mode) |
| Overload tolerance | 105% ~ 125% in 10 minutes or 1 minute, 125% ~ 150% in 30 seconds, >150% in 0.5 seconds |
| Output power supply | Terminal box |
| BYPASS MODE | |
| Automatically switch to Bypass mode | Overload, UPS failure |
| Service Switch | Optional on request |
| EMERGENCY OFF FUNCTION (EPO) | |
| Power UPS Emergency Off Function (EPO) | Optional on request |
| ẮQUI | |
| Battery type | 12 VDC, airtight, maintenance free, over 3 years lifespan |
| Save time | Depending on external battery capacity and load capacity used. |
| Battery charge time | Depending on external battery capacity |
| interface | |
| Dashboard | Start button / Self test / Buzzer off / Power off button |
| Status LED | Grid power mode, battery mode, Bypass mode, load capacity, battery capacity, failure status report. |
| Communication port | RS232, expansion slot |
| Management software | Winpower system automatic shutdown and power management software compatible with Window, Linux, Unix, Sun |
| Switching time | 0 ms |
| N+X parallel connection function | Make-to-order |
| OPERATING ENVIRONMENT | |
| Operating ambient temperature | 0 ~ 40oc |
| Operating ambient humidity | 20% ~ 90%, no condensation. |
| Cooling system | Air convection fan |
| STANDARD | |
| Noise when operating | |
| Electromagnetic field (EMS) | IEC 61000-4-2 Level 4 (ESD) |
| IEC 61000-4-3 Level 3 (RS) | |
| IEC 61000-4-4 Level 4 (EFT) | |
| IEC 61000-4-5 Level 4 (Surge) | |
| EMI safety standard | IEC62040-2, with input current ≥ 25A |
| Safety standards | IEC62040-1 |
| SIZE / WEIGHT | |
| Dimensions (R x D x C) (mm) | 212 x 500 x 420 |
| Net weight (kg) | 16.9 |