Follow Us

Card AS400

Mua Ngay

AS400
PRICE : PLEASE CALL
(not include VAT)
The AS400 port is the output of the relays (relays) and the remote control (Shutdown) UPS for industrial monitoring and control applications as well as a number of other applications.

Pinout of AS400 port relays

Function of pins of AS400 SANTAK card

FOOT ORDER

FUNCTIONALITY

I/O

Leg 1

UPS error

O

Leg 2

General warning of errors

O

Leg 3

GND

I

Foot 4

Remote turn off

I

Pin 5

Common relays

O

Length 6

UPS works Bypass

O

Foot 7

Battery is weak

O

Pin 8

UPS enabled

O

Pin 9

Mass power failure

O

 

Power parameter DB-9 port of AS400 card

PARAMETER

SYMBOL

MAX

UNIT

Relay

DC Voltage

VDC

24

V

DC Current

IDC

1.0

A

Diode

Revese Voltage

VR

6

V

Forward Current

IF

80

mA

Peak Forward Current

IF(peak)

1

A

>/div>
 

The remote shutdown signal is put on pins 3 and 4 high (5Vdc) and kept for 3~10 seconds, the UPS will turn off.

Default Function Description for AS400 SANTAK Gateway:

IMPACT

EVENT NOTICE

Pins 1, 5 closed UPS has an internal error
Pins 2, 5 closed UPS error, mains power failure, low battery, UPS bypass operation
Pins 6, 5 closed UPS Operation Bypass
Pins 7, 5 closed Battery is weak
Pins 8, 5 closed UPS working under normal conditions
Pins 9, 5 closed Mass power failure

 

Mains fault can be: loss of input mains power to UPS, wrong phase order, out of range (higher or lower) input voltage of UPS operation, out of range frequency (higher or lower) ) UPS operating range…